Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- SCHNEIDER
Technical specifications
Integrated earth fault protection
No
Rated permanent current Iu
1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Screw connection
DIN rail (top hat rail) mounting optional
No
Adjustment range undelayed short-circuit release
2000 - 15000A
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
600 - 10000A
Number of auxiliary contacts as normally open contact
0
Overload release current setting
400 - 1000A
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
Yes
Number of poles
3
Position of connection for main current circuit
Front side
Type of control element
Toggle
With integrated under voltage release
No
Complete device with protection unit
Yes
Degree of protection (IP)
IP40
Motor drive integrated
No
Motor drive optional
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
33560
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- SCHNEIDER
Technical specifications
Integrated earth fault protection
Rated permanent current Iu
1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Screw connection
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
2000 .. 15000A
Number of auxiliary contacts as normally closed contact
0
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
600 .. 10000A
Number of auxiliary contacts as normally open contact
0
Overload release current setting
400 .. 1000A
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
Number of poles
3
Position of connection for main current circuit
Front side
Type of control element
Toggle
With integrated under voltage release
Complete device with protection unit
Degree of protection (IP)
IP40
Motor drive integrated
Motor drive optional
From same serie