- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- SCHNEIDER
Technical specifications
Rated permanent current Iu
800A
Overload release current setting
320 - 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range undelayed short-circuit release
1600 - 12000A
Power loss
60W
Number of auxiliary contacts as change-over contact
0
Type of electrical connection of main circuit
Screw connection
With integrated under voltage release
No
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
No
With switched-off indicator
Yes
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
No
Complete device with protection unit
Yes
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Front side
Number of poles
3
Type of control element
Toggle
Adjustment range short-term delayed short-circuit release
480 - 8000A
Motor drive optional
Yes
Degree of protection (IP)
IP40
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
33554
![Main Product Image](https://assets.aleta.hr/300x300/e611d653-1a12-4fe1-a319-a05f87e77bfa_optimized.webp)
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- SCHNEIDER
Technical specifications
Rated permanent current Iu
800A
Overload release current setting
320 .. 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range undelayed short-circuit release
1600 .. 12000A
Power loss
60W
Number of auxiliary contacts as change-over contact
0
Type of electrical connection of main circuit
Screw connection
With integrated under voltage release
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
With switched-off indicator
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
Complete device with protection unit
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Front side
Number of poles
3
Type of control element
Toggle
Adjustment range short-term delayed short-circuit release
480 .. 8000A
Motor drive optional
Degree of protection (IP)
IP40