Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- SCHNEIDER
Technical specifications
Overload release current setting
- - -A
Adjustment range undelayed short-circuit release
- - -A
Adjustment range short-term delayed short-circuit release
- - -A
Rated permanent current Iu
1250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally closed contact
0
With integrated under voltage release
No
Integrated earth fault protection
No
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
Yes
Number of poles
4
Device construction
Built-in device fixed built-in technique
Type of control element
Toggle
Motor drive integrated
No
Position of connection for main current circuit
Front side
Motor drive optional
Yes
Complete device with protection unit
No
Degree of protection (IP)
IP40
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
33254
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- SCHNEIDER
Technical specifications
Overload release current setting
- .. -A
Adjustment range undelayed short-circuit release
- .. -A
Adjustment range short-term delayed short-circuit release
- .. -A
Rated permanent current Iu
1250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Bolt connection
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
With integrated under voltage release
Integrated earth fault protection
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
0
With switched-off indicator
Number of poles
4
Device construction
Built-in device fixed built-in technique
Type of control element
Toggle
Motor drive integrated
Position of connection for main current circuit
Front side
Motor drive optional
Complete device with protection unit
Degree of protection (IP)
IP40
From same serie
We use cookies to enhance your experience.