

Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- SCHNEIDER
Technical specifications
Current limiting class
-
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
-kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
-kA
Rated current
125A
Number of protected poles
4
Release characteristic
B
Built-in depth
47mm
Rated voltage
400V
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
50kA
Voltage type
AC/DC
Rated insulation voltage Ui
690V
Frequency
50 - 60Hz
Rated impulse withstand voltage Uimp
8kV
Over voltage category
4
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
25kA
Flush-mounted installation
No
Concurrently switching neutral conductor
Yes
Additional equipment possible
Yes
Connectable conductor cross section multi-wired
10 - 50mm²
Pollution degree
3
Degree of protection (IP)
IP20
Ambient temperature during operating
-30 - 70°C
Number of poles (total)
4
Explosion-proof
No
Connectable conductor cross section solid-core
16 - 70mm²
Width in number of modular spacings
6
From same serie
18668

Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- SCHNEIDER
Technical specifications
Current limiting class
-
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
-kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
-kA
Rated current
125A
Number of protected poles
4
Release characteristic
B
Built-in depth
47mm
Rated voltage
400V
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
50kA
Voltage type
AC/DC
Rated insulation voltage Ui
690V
Frequency
50 .. 60Hz
Rated impulse withstand voltage Uimp
8kV
Over voltage category
4
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
25kA
Flush-mounted installation
Concurrently switching neutral conductor
Additional equipment possible
Connectable conductor cross section multi-wired
10 .. 50mm²
Pollution degree
3
Degree of protection (IP)
IP20
Ambient temperature during operating
-30 .. 70°C
Number of poles (total)
4
Explosion-proof
Connectable conductor cross section solid-core
16 .. 70mm²
Width in number of modular spacings
6
From same serie
We use cookies to enhance your experience.