Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- ABB
Technical specifications
Degree of protection (IP)
IP20
Mounting method
DIN rail (top hat rail) 35 mm
Construction size
3 modular spacing
Number of conductors (without earthing)
2
Max. continuous voltage AC
-V
Signalling at the device
Optic
Max. continuous voltage DC
1100V
Voltage protection level
2.5kV
Nominal voltage AC
-V
Voltage protection level L-N
2.5kV
Max. conductor cross section flexible (fine-strand)
25mm²
Max. conductor cross section solid (solid, stranded)
35mm²
Integrated backup fuse
No
Nominal voltage DC
1100V
With remote signalling contact
No
Voltage protection level N-PE
2.5kV
Nominal discharge surge current (8/20)
20kA
System configuration DC
Yes
System configuration TN
No
System configuration TN-S
No
System configuration IT
No
System configuration TT
No
System configuration TN-C
No
System configuration other
No
System configuration TN-C-S
No
Max. PV-voltage
1100V
Category type 2
Yes
Max. discharge surge current (8/20)
40kA
Short-circuit breaking capacity (Isccr)
10kA
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
2CTB804153R2500 | OVR PV T2 40-1000 P TS QS

Details
- Earthing, lightning and surge protection
- Surge protection device for power supply systems
- 1 KOM
- ABB
Technical specifications
Degree of protection (IP)
IP20
Mounting method
DIN rail (top hat rail) 35 mm
Construction size
3 modular spacing
Number of conductors (without earthing)
2
Max. continuous voltage AC
-V
Signalling at the device
Optic
Max. continuous voltage DC
1100V
Voltage protection level
2.5kV
Nominal voltage AC
-V
Voltage protection level L-N
2.5kV
Max. conductor cross section flexible (fine-strand)
25mm²
Max. conductor cross section solid (solid, stranded)
35mm²
Integrated backup fuse
Nominal voltage DC
1100V
With remote signalling contact
Voltage protection level N-PE
2.5kV
Nominal discharge surge current (8/20)
20kA
System configuration DC
System configuration TN
System configuration TN-S
System configuration IT
System configuration TT
System configuration TN-C
System configuration other
System configuration TN-C-S
Max. PV-voltage
1100V
Category type 2
Max. discharge surge current (8/20)
40kA
Short-circuit breaking capacity (Isccr)
10kA