Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
160A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 - 690V
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
1920 - 1920A
Adjustment range short-term delayed short-circuit release
160 - 1600A
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
Yes
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
No
With integrated under voltage release
No
Number of poles
4
Position of connection for main current circuit
Front side
Integrated earth fault protection
No
Overload release current setting
80 - 160A
Type of control element
Rocker lever
Complete device with protection unit
Yes
Degree of protection (IP)
IP20
Motor drive optional
Yes
Motor drive integrated
No
Device construction
Built-in device plug-in technique
Type of electrical connection of main circuit
Screw connection
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
Related products
From same serie
NZML2-4-VE160-SVE

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- EATON
Technical specifications
Rated permanent current Iu
160A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 .. 690V
Number of auxiliary contacts as change-over contact
0
Number of auxiliary contacts as normally closed contact
0
Adjustment range undelayed short-circuit release
1920 .. 1920A
Adjustment range short-term delayed short-circuit release
160 .. 1600A
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
With integrated under voltage release
Number of poles
4
Position of connection for main current circuit
Front side
Integrated earth fault protection
Overload release current setting
80 .. 160A
Type of control element
Rocker lever
Complete device with protection unit
Degree of protection (IP)
IP20
Motor drive optional
Motor drive integrated
Device construction
Built-in device plug-in technique
Type of electrical connection of main circuit
Screw connection
From same serie