Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- EATON
Technical specifications
Built-in depth
70.5mm
Rated current
63A
Rated voltage
400V
Number of protected poles
3
Number of poles (total)
3
Voltage type
AC
Current limiting class
3
Rated impulse withstand voltage Uimp
4kV
Rated insulation voltage Ui
440V
Frequency
50 - 60Hz
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
10kA
Flush-mounted installation
No
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
6kA
Concurrently switching neutral conductor
No
Power loss
16.6W
Additional equipment possible
Yes
Over voltage category
3
Width in number of modular spacings
3
Degree of protection (IP)
IP20
Ambient temperature during operating
-25 - 75°C
Release characteristic
D
Pollution degree
2
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
10kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
6kA
Connectable conductor cross section solid-core
1 - 25mm²
Explosion-proof
No
Connectable conductor cross section multi-wired
1 - 25mm²
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
Related products
From same serie
FAZ-D63/3

Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- EATON
Technical specifications
Built-in depth
70.5mm
Rated current
63A
Rated voltage
400V
Number of protected poles
3
Number of poles (total)
3
Voltage type
AC
Current limiting class
3
Rated impulse withstand voltage Uimp
4kV
Rated insulation voltage Ui
440V
Frequency
50 .. 60Hz
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
10kA
Flush-mounted installation
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
6kA
Concurrently switching neutral conductor
Power loss
16.6W
Additional equipment possible
Over voltage category
3
Width in number of modular spacings
3
Degree of protection (IP)
IP20
Ambient temperature during operating
-25 .. 75°C
Release characteristic
D
Pollution degree
2
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
10kA
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
6kA
Connectable conductor cross section solid-core
1 .. 25mm²
Explosion-proof
Connectable conductor cross section multi-wired
1 .. 25mm²
From same serie
Related products
We use cookies to enhance your experience.