Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- EATON
Technical specifications
Rated voltage
400V
Rated impulse withstand voltage Uimp
4kV
Release characteristic
B
Rated current
32A
Built-in depth
75mm
Rated insulation voltage Ui
440V
Number of protected poles
3
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
25kA
Flush-mounted installation
No
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
0kA
Current limiting class
3
Frequency
50 - 60Hz
Voltage type
AC
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
25kA
Concurrently switching neutral conductor
No
Pollution degree
2
Over voltage category
3
Connectable conductor cross section multi-wired
2.5 - 50mm²
Connectable conductor cross section solid-core
2.5 - 50mm²
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
0kA
Explosion-proof
No
Additional equipment possible
Yes
Degree of protection (IP)
IP20
Width in number of modular spacings
4.5
Number of poles (total)
3
Ambient temperature during operating
-25 - 55°C
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
AZ-3-B32

Details
- Circuit breakers and fuses
- Miniature circuit breaker (MCB)
- 1 KOM
- EATON
Technical specifications
Rated voltage
400V
Rated impulse withstand voltage Uimp
4kV
Release characteristic
B
Rated current
32A
Built-in depth
75mm
Rated insulation voltage Ui
440V
Number of protected poles
3
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 400 V
25kA
Flush-mounted installation
Rated short-circuit breaking capacity Icn according to EN 60898 at 230 V
0kA
Current limiting class
3
Frequency
50 .. 60Hz
Voltage type
AC
Rated short-circuit breaking capacity Icu according to IEC 60947-2 at 230 V
25kA
Concurrently switching neutral conductor
Pollution degree
2
Over voltage category
3
Connectable conductor cross section multi-wired
2.5 .. 50mm²
Connectable conductor cross section solid-core
2.5 .. 50mm²
Rated short-circuit breaking capacity Icn according to EN 60898 at 400 V
0kA
Explosion-proof
Additional equipment possible
Degree of protection (IP)
IP20
Width in number of modular spacings
4.5
Number of poles (total)
3
Ambient temperature during operating
-25 .. 55°C
From same serie