Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
5000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
2000.0 - 5000A
Integrated earth fault protection
No
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range short-term delayed short-circuit release
3000.0 - 50000A
With switched-off indicator
Yes
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Type of control element
Push button
Adjustment range undelayed short-circuit release
7500.0 - 75000A
Motor drive optional
Yes
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Motor drive integrated
No
Rated voltage
690 - 690V
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA073335R1 | E6.2H/F 5000 EKIP TOUCH LSI 4P W

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
5000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
2000.0 .. 5000A
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
3000.0 .. 50000A
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Type of control element
Push button
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Motor drive optional
Degree of protection (IP)
IP30
Complete device with protection unit
Motor drive integrated
Rated voltage
690 .. 690V
From same serie