

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
1600.0 - 4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Rated permanent current Iu
4000A
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release
6000.0 - 60000A
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Yes
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Position of connection for main current circuit
Connection at separate chassis part
Motor drive optional
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
From same serie
1SDA073313R1 | E6.2V/F 4000 EKIP DIP LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
1600.0 .. 4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Rated permanent current Iu
4000A
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Position of connection for main current circuit
Connection at separate chassis part
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP30
Complete device with protection unit
From same serie
We use cookies to enhance your experience.