Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
4000A
Integrated earth fault protection
No
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Overload release current setting
1600.0 - 4000A
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Yes
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of poles
4
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Yes
Type of control element
Push button
With under voltage release
No
Complete device with protection unit
Yes
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Motor drive integrated
No
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA073304R1 | E6.2H/F 4000 EKIP TOUCH LI 4P WM

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
4000A
Integrated earth fault protection
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Overload release current setting
1600.0 .. 4000A
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of poles
4
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Type of control element
Push button
With under voltage release
Complete device with protection unit
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Motor drive integrated
From same serie