Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
3000.0 - 50000A
Adjustment range undelayed short-circuit release
7500.0 - 75000A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated permanent current Iu
5000A
Type of control element
Push button
With under voltage release
No
Integrated earth fault protection
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
Overload release current setting
2000.0 - 5000A
Rated voltage
690 - 690V
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
Yes
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Motor drive optional
Yes
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
From same serie
1SDA073250R1 | E6.2H 5000 EKIP G HI-TOUCH LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
3000.0 .. 50000A
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated permanent current Iu
5000A
Type of control element
Push button
With under voltage release
Integrated earth fault protection
Motor drive integrated
Degree of protection (IP)
IP30
Overload release current setting
2000.0 .. 5000A
Rated voltage
690 .. 690V
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Motor drive optional
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
From same serie