Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated voltage
690 - 690V
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Yes
Integrated earth fault protection
Yes
Number of poles
4
Motor drive integrated
No
Type of control element
Push button
Complete device with protection unit
Yes
Position of connection for main current circuit
Connection at separate chassis part
Motor drive optional
Yes
Degree of protection (IP)
IP30
With under voltage release
No
DIN rail (top hat rail) mounting optional
No
Rated permanent current Iu
2500A
Overload release current setting
1000.0 - 2500A
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA073070R1 | E2.2H 2500 EKIP G HI-TOUCH LSIG

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated voltage
690 .. 690V
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Integrated earth fault protection
Number of poles
4
Motor drive integrated
Type of control element
Push button
Complete device with protection unit
Position of connection for main current circuit
Connection at separate chassis part
Motor drive optional
Degree of protection (IP)
IP30
With under voltage release
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
2500A
Overload release current setting
1000.0 .. 2500A
From same serie