Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated permanent current Iu
2500A
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Number of poles
4
DIN rail (top hat rail) mounting optional
No
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Motor drive integrated
No
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Complete device with protection unit
Yes
Overload release current setting
1000.0 - 2500A
Motor drive optional
Yes
Type of control element
Push button
Integrated earth fault protection
No
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
From same serie
1SDA073065R1 | E2.2H 2500 EKIP TOUCH LSI 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated permanent current Iu
2500A
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Number of poles
4
DIN rail (top hat rail) mounting optional
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Motor drive integrated
Number of auxiliary contacts as normally open contact
0
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Complete device with protection unit
Overload release current setting
1000.0 .. 2500A
Motor drive optional
Type of control element
Push button
Integrated earth fault protection
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
From same serie
We use cookies to enhance your experience.