1SDA073018R1 | E2.2N 2000 EKIP HI-TOUCH LSI 4P
Code: 1615694
Sign in or create an account for lower prices and other benefits
Code: 1615694
Sign in or create an account for lower prices and other benefits
Technical specifications
Rated permanent current Iu
2000A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
800.0 - 2000A
Adjustment range short-term delayed short-circuit release
1200.0 - 20000A
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Power loss
450W
Device construction
Built-in device slide-in technique (withdrawable)
Integrated earth fault protection
No
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
With integrated under voltage release
No
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Zagreb:
0 pcs
Zadar:
0 pcs
1SDA073018R1 | E2.2N 2000 EKIP HI-TOUCH LSI 4P
Code
1615694
Catalog number
1SDA073018R1
Type
Power circuit-breaker for trafo/generator/installation protection
Manufacturer
ABBSerie
-
9.807,87 €
Total stock:
0 PCS
2000A
690 .. 690V
66kA
800.0 .. 2000A
1200.0 .. 20000A
3000.0 .. 30000A
450W
Built-in device slide-in technique (withdrawable)
Connection at separate chassis part
0
0
4
4
Connection at separate chassis part
Push button
IP30
We use cookies to enhance your experience.