Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Rated voltage
690 - 690V
Device construction
Built-in device slide-in technique (withdrawable)
Rated permanent current Iu
1600A
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
640.0 - 1600A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Integrated earth fault protection
No
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Motor drive optional
Yes
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Number of poles
4
Motor drive integrated
No
From same serie
1SDA072962R1 | E2.2B 1600 EKIP DIP LSI 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Rated voltage
690 .. 690V
Device construction
Built-in device slide-in technique (withdrawable)
Rated permanent current Iu
1600A
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
640.0 .. 1600A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Integrated earth fault protection
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Motor drive optional
Complete device with protection unit
Degree of protection (IP)
IP30
Number of poles
4
Motor drive integrated
From same serie