Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
800A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated voltage
690 - 690V
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
No
Overload release current setting
320.0 - 800A
Integrated earth fault protection
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
DIN rail (top hat rail) mounting optional
No
Adjustment range undelayed short-circuit release
1200.0 - 12000A
With switched-off indicator
Yes
With under voltage release
No
Number of poles
4
Motor drive optional
Yes
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Position of connection for main current circuit
Connection at separate chassis part
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA072900R1 | E2.2H 800 EKIP G HI-TOUCH LSIG 4

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
800A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated voltage
690 .. 690V
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
Overload release current setting
320.0 .. 800A
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
With switched-off indicator
With under voltage release
Number of poles
4
Motor drive optional
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive integrated
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Position of connection for main current circuit
Connection at separate chassis part
From same serie