Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
800A
Overload release current setting
320.0 - 800A
Rated voltage
690 - 690V
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
No
Degree of protection (IP)
IP30
Type of control element
Push button
Motor drive optional
Yes
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range undelayed short-circuit release
1200.0 - 12000A
With switched-off indicator
Yes
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
4
Complete device with protection unit
Yes
From same serie
1SDA072895R1 | E2.2H 800 EKIP TOUCH LSI 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
800A
Overload release current setting
320.0 .. 800A
Rated voltage
690 .. 690V
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Motor drive integrated
Degree of protection (IP)
IP30
Type of control element
Push button
Motor drive optional
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
With switched-off indicator
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
4
Complete device with protection unit