Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Adjustment range short-term delayed short-circuit release
750.0 - 12500A
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Type of electrical connection of main circuit
Connection at separate chassis part
Rated permanent current Iu
1250A
Rated voltage
690 - 690V
DIN rail (top hat rail) mounting optional
No
Device construction
Built-in device slide-in technique (withdrawable)
Overload release current setting
500.0 - 1250A
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Integrated earth fault protection
Yes
With switched-off indicator
Yes
Number of poles
4
Degree of protection (IP)
IP30
With under voltage release
No
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive optional
Yes
From same serie
1SDA072816R1 | E1.2C 1250 EKIP TOUCH LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Type of electrical connection of main circuit
Connection at separate chassis part
Rated permanent current Iu
1250A
Rated voltage
690 .. 690V
DIN rail (top hat rail) mounting optional
Device construction
Built-in device slide-in technique (withdrawable)
Overload release current setting
500.0 .. 1250A
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Integrated earth fault protection
With switched-off indicator
Number of poles
4
Degree of protection (IP)
IP30
With under voltage release
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive optional
From same serie