Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
With integrated under voltage release
No
Overload release current setting
400.0 - 1000A
Rated voltage
690 - 690V
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
No
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Device construction
Built-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Yes
Motor drive optional
Yes
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Degree of protection (IP)
IP30
Rated permanent current Iu
1000A
Number of poles
4
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
Motor drive integrated
No
From same serie
1SDA072771R1 | E1.2C 1000 EKIP DIP LI 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
With integrated under voltage release
Overload release current setting
400.0 .. 1000A
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Device construction
Built-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Number of auxiliary contacts as normally open contact
0
Complete device with protection unit
Motor drive optional
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Degree of protection (IP)
IP30
Rated permanent current Iu
1000A
Number of poles
4
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
With switched-off indicator
Motor drive integrated
From same serie