Technical specifications
With integrated under voltage release
No
Type of electrical connection of main circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated permanent current Iu
5000A
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
7500.0 - 75000A
Adjustment range short-term delayed short-circuit release
3000.0 - 50000A
Integrated earth fault protection
Yes
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Motor drive optional
Yes
Number of poles
3
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
Type of control element
Push button
Degree of protection (IP)
IP30
Motor drive integrated
No
Overload release current setting
2000.0 - 5000A
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
From same serie
1SDA072630R1 | E6.2V 5000 EKIP G HI-TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Type of electrical connection of main circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated permanent current Iu
5000A
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Adjustment range short-term delayed short-circuit release
3000.0 .. 50000A
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Motor drive optional
Number of poles
3
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Type of control element
Push button
Degree of protection (IP)
IP30
Motor drive integrated
Overload release current setting
2000.0 .. 5000A
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting