Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
2000.0 - 5000A
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
3000.0 - 50000A
Adjustment range undelayed short-circuit release
7500.0 - 75000A
Rated permanent current Iu
5000A
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
No
Device construction
Built-in device slide-in technique (withdrawable)
With switched-off indicator
Yes
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Rated voltage
690 - 690V
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Motor drive optional
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
Number of poles
3
Complete device with protection unit
Yes
From same serie
1SDA072625R1 | E6.2V 5000 EKIP TOUCH LSI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Type of electrical connection of main circuit
Connection at separate chassis part
Overload release current setting
2000.0 .. 5000A
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
3000.0 .. 50000A
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Rated permanent current Iu
5000A
Number of auxiliary contacts as normally open contact
0
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
With switched-off indicator
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP30
Number of poles
3
Complete device with protection unit
From same serie