Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Motor drive integrated
No
DIN rail (top hat rail) mounting optional
No
Degree of protection (IP)
IP30
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Adjustment range undelayed short-circuit release
6000.0 - 60000A
With switched-off indicator
Yes
Overload release current setting
1600.0 - 4000A
Type of electrical connection of main circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Motor drive optional
Yes
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
Rated permanent current Iu
4000A
Integrated earth fault protection
Yes
From same serie
1SDA072583R1 | E6.2H 4000 EKIP DIP LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Motor drive integrated
DIN rail (top hat rail) mounting optional
Degree of protection (IP)
IP30
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
With switched-off indicator
Overload release current setting
1600.0 .. 4000A
Type of electrical connection of main circuit
Connection at separate chassis part
Complete device with protection unit
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Motor drive optional
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
Rated permanent current Iu
4000A
Integrated earth fault protection
From same serie