

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
4000A
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Integrated earth fault protection
Yes
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Overload release current setting
1600.0 - 4000A
Rated voltage
690 - 690V
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Complete device with protection unit
Yes
Number of poles
3
Motor drive integrated
No
Motor drive optional
Yes
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally closed contact
0
From same serie
1SDA072550R1 | E4.2N 4000 EKIP G HI-TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
4000A
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Integrated earth fault protection
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Overload release current setting
1600.0 .. 4000A
Rated voltage
690 .. 690V
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Complete device with protection unit
Number of poles
3
Motor drive integrated
Motor drive optional
Position of connection for main current circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally closed contact
0
From same serie
We use cookies to enhance your experience.