

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
1280.0 - 3200A
Adjustment range short-term delayed short-circuit release
1920.0 - 32000A
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device slide-in technique (withdrawable)
With switched-off indicator
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
No
DIN rail (top hat rail) mounting optional
No
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Complete device with protection unit
Yes
Number of poles
3
Motor drive optional
Yes
Motor drive integrated
No
With under voltage release
No
Rated permanent current Iu
3200A
Rated voltage
690 - 690V
Degree of protection (IP)
IP30
From same serie
1SDA072528R1 | E4.2V 3200 EKIP HI-TOUCH LSI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
1280.0 .. 3200A
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device slide-in technique (withdrawable)
With switched-off indicator
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Complete device with protection unit
Number of poles
3
Motor drive optional
Motor drive integrated
With under voltage release
Rated permanent current Iu
3200A
Rated voltage
690 .. 690V
Degree of protection (IP)
IP30
From same serie
We use cookies to enhance your experience.