Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
3200A
Overload release current setting
1280.0 - 3200A
Adjustment range short-term delayed short-circuit release
1920.0 - 32000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Position of connection for main current circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
4800.0 - 48000A
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
Rated voltage
690 - 690V
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA072523R1 | E4.2V 3200 EKIP DIP LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
3200A
Overload release current setting
1280.0 .. 3200A
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Position of connection for main current circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
DIN rail (top hat rail) mounting optional
With switched-off indicator
Type of electrical connection of main circuit
Connection at separate chassis part
Rated voltage
690 .. 690V
Type of control element
Push button
Complete device with protection unit
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
From same serie