Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Adjustment range short-term delayed short-circuit release
1920.0 - 32000A
Overload release current setting
1280.0 - 3200A
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Rated permanent current Iu
3200A
Integrated earth fault protection
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
Yes
With switched-off indicator
Yes
Number of poles
3
Type of control element
Push button
Motor drive optional
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
From same serie
1SDA072509R1 | E4.2S 3200 EKIP HI-TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Overload release current setting
1280.0 .. 3200A
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Rated permanent current Iu
3200A
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
With switched-off indicator
Number of poles
3
Type of control element
Push button
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP30
From same serie