Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
3200A
Overload release current setting
1280.0 - 3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Number of poles
3
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
No
Motor drive optional
Yes
Complete device with protection unit
Yes
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
1920.0 - 32000A
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA072497R1 | E4.2N 3200 EKIP G TOUCH LSIG 3P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
3200A
Overload release current setting
1280.0 .. 3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Number of poles
3
DIN rail (top hat rail) mounting optional
With switched-off indicator
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
Motor drive optional
Complete device with protection unit
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A