Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Rated permanent current Iu
2000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
800.0 - 2000A
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Yes
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Adjustment range short-term delayed short-circuit release
1200.0 - 20000A
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device slide-in technique (withdrawable)
Type of control element
Push button
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA072459R1 | E4.2V 2000 EKIP HI-TOUCH LSIG 3P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Rated permanent current Iu
2000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Overload release current setting
800.0 .. 2000A
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Adjustment range short-term delayed short-circuit release
1200.0 .. 20000A
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device slide-in technique (withdrawable)
Type of control element
Push button
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
Complete device with protection unit