Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Rated permanent current Iu
2000A
Overload release current setting
800.0 - 2000A
Rated voltage
690 - 690V
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range short-term delayed short-circuit release
1200.0 - 20000A
Integrated earth fault protection
No
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Yes
Complete device with protection unit
Yes
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
With under voltage release
No
Type of control element
Push button
Degree of protection (IP)
IP30
DIN rail (top hat rail) mounting optional
No
Motor drive integrated
No
Motor drive optional
Yes
From same serie
1SDA072372R1 | E2.2B 2000 EKIP DIP LSI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Rated permanent current Iu
2000A
Overload release current setting
800.0 .. 2000A
Rated voltage
690 .. 690V
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
Adjustment range short-term delayed short-circuit release
1200.0 .. 20000A
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Complete device with protection unit
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
With under voltage release
Type of control element
Push button
Degree of protection (IP)
IP30
DIN rail (top hat rail) mounting optional