Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
640.0 - 1600A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device slide-in technique (withdrawable)
Integrated earth fault protection
Yes
Number of poles
3
Rated permanent current Iu
1600A
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
Motor drive optional
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
From same serie
1SDA072347R1 | E2.2N 1600 EKIP G TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
640.0 .. 1600A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device slide-in technique (withdrawable)
Integrated earth fault protection
Number of poles
3
Rated permanent current Iu
1600A
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
Motor drive optional
Degree of protection (IP)
IP30
Motor drive integrated
From same serie