Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 - 690V
Rated permanent current Iu
1600A
Overload release current setting
640.0 - 1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Integrated earth fault protection
No
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
With under voltage release
No
Motor drive optional
Yes
Number of poles
3
Type of control element
Push button
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
Position of connection for main current circuit
Connection at separate chassis part
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA072338R1 | E2.2B 1600 EKIP HI-TOUCH LSI 3P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 .. 690V
Rated permanent current Iu
1600A
Overload release current setting
640.0 .. 1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
With switched-off indicator
With under voltage release
Motor drive optional
Number of poles
3
Type of control element
Push button
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive integrated
Position of connection for main current circuit
Connection at separate chassis part
From same serie
We use cookies to enhance your experience.