Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1250A
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
750.0 - 12500A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Overload release current setting
500.0 - 1250A
Integrated earth fault protection
Yes
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
No
Device construction
Built-in device slide-in technique (withdrawable)
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Motor drive optional
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
From same serie
1SDA072326R1 | E2.2H 1250 EKIP TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1250A
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Type of electrical connection of main circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Overload release current setting
500.0 .. 1250A
Integrated earth fault protection
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
Device construction
Built-in device slide-in technique (withdrawable)
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Number of poles
3
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP30
From same serie