Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Integrated earth fault protection
No
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Overload release current setting
320.0 - 800A
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Connection at separate chassis part
With switched-off indicator
Yes
Number of poles
3
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Motor drive optional
Yes
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive integrated
No
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
From same serie
1SDA072265R1 | E2.2H 800 EKIP TOUCH LSI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Overload release current setting
320.0 .. 800A
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Connection at separate chassis part
With switched-off indicator
Number of poles
3
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Motor drive optional
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive integrated
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Connection at separate chassis part