Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
With integrated under voltage release
No
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Overload release current setting
320.0 - 800A
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Type of control element
Push button
Type of electrical connection of main circuit
Connection at separate chassis part
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Motor drive integrated
No
Number of poles
3
Integrated earth fault protection
No
Degree of protection (IP)
IP30
Motor drive optional
Yes
From same serie
1SDA072261R1 | E2.2H 800 EKIP DIP LI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
With integrated under voltage release
Rated permanent current Iu
800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Overload release current setting
320.0 .. 800A
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Type of control element
Push button
Type of electrical connection of main circuit
Connection at separate chassis part
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Motor drive integrated
Number of poles
3
Integrated earth fault protection
Degree of protection (IP)
IP30
Motor drive optional
From same serie