Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
640.0 - 1600A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Rated permanent current Iu
1600A
DIN rail (top hat rail) mounting optional
No
Type of control element
Push button
Integrated earth fault protection
No
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Motor drive integrated
No
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
Yes
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
Rated voltage
690 - 690V
Degree of protection (IP)
IP30
With under voltage release
No
Motor drive optional
Yes
From same serie
1SDA072232R1 | E1.2N 1600 EKIP DIP LSI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
640.0 .. 1600A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Rated permanent current Iu
1600A
DIN rail (top hat rail) mounting optional
Type of control element
Push button
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Motor drive integrated
Device construction
Built-in device slide-in technique (withdrawable)
Complete device with protection unit
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
3
Rated voltage
690 .. 690V
Degree of protection (IP)
IP30