

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated permanent current Iu
6300A
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Integrated earth fault protection
No
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Position of connection for main current circuit
Back side
Motor drive integrated
No
Adjustment range short-term delayed short-circuit release
3780.0 - 63000A
Complete device with protection unit
Yes
Motor drive optional
Yes
With switched-off indicator
Yes
Overload release current setting
2520.0 - 6300A
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 - 690V
Degree of protection (IP)
IP30
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device fixed built-in technique
Number of poles
4
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA072015R1 | E6.2H/F 6300 EKIP TOUCH LSI 4P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated permanent current Iu
6300A
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Position of connection for main current circuit
Back side
Motor drive integrated
Adjustment range short-term delayed short-circuit release
3780.0 .. 63000A
Complete device with protection unit
Motor drive optional
With switched-off indicator
Overload release current setting
2520.0 .. 6300A
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 .. 690V
Degree of protection (IP)
IP30
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
Number of poles
4
From same serie
We use cookies to enhance your experience.