

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Position of connection for main current circuit
Back side
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
Yes
Degree of protection (IP)
IP30
Number of poles
4
Rated voltage
690 - 690V
Complete device with protection unit
Yes
Motor drive integrated
No
Overload release current setting
1600.0 - 4000A
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Rated permanent current Iu
4000A
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device fixed built-in technique
Motor drive optional
Yes
Number of auxiliary contacts as normally open contact
0
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA071846R1 | E4.2H 4000 EKIP TOUCH LSIG 4P FH

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Position of connection for main current circuit
Back side
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
Degree of protection (IP)
IP30
Number of poles
4
Rated voltage
690 .. 690V
Complete device with protection unit
Motor drive integrated
Overload release current setting
1600.0 .. 4000A
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as normally closed contact
0
Type of control element
Push button
Rated permanent current Iu
4000A
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device fixed built-in technique
Motor drive optional
Number of auxiliary contacts as normally open contact
0
From same serie
We use cookies to enhance your experience.