Technical specifications

With integrated under voltage release

No

Rated permanent current Iu

2500A

Adjustment range short-term delayed short-circuit release

1500.0 - 25000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Overload release current setting

1000.0 - 2500A

Adjustment range undelayed short-circuit release

3750.0 - 37500A

Integrated earth fault protection

No

Rated voltage

690 - 690V

Type of electrical connection of main circuit

Bolt connection

Suitable for DIN rail (top hat rail) mounting

No

Number of auxiliary contacts as normally closed contact

0

DIN rail (top hat rail) mounting optional

No

Device construction

Built-in device fixed built-in technique

Type of control element

Push button

With switched-off indicator

Yes

Number of poles

4

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Back side

Motor drive integrated

No

Degree of protection (IP)

IP30

Motor drive optional

Yes

Number of auxiliary contacts as normally open contact

0

Complete device with protection unit

Yes


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA071755R1 | E4.2V 2500 EKIP TOUCH LSI 4P FHR

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

2500A

Adjustment range short-term delayed short-circuit release

1500.0 .. 25000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Overload release current setting

1000.0 .. 2500A

Adjustment range undelayed short-circuit release

3750.0 .. 37500A

Integrated earth fault protection

Rated voltage

690 .. 690V

Type of electrical connection of main circuit

Bolt connection

Suitable for DIN rail (top hat rail) mounting

Number of auxiliary contacts as normally closed contact

0

DIN rail (top hat rail) mounting optional

Device construction

Built-in device fixed built-in technique

Type of control element

Push button

With switched-off indicator

Number of poles

4

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Back side

Motor drive integrated

Degree of protection (IP)

IP30

Motor drive optional

Number of auxiliary contacts as normally open contact