Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
2500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Rated voltage
690 - 690V
Integrated earth fault protection
No
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
With switched-off indicator
Yes
Number of poles
4
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Motor drive optional
Yes
Degree of protection (IP)
IP30
Adjustment range undelayed short-circuit release
3750.0 - 37500A
DIN rail (top hat rail) mounting optional
No
Position of connection for main current circuit
Back side
Type of control element
Push button
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
Motor drive integrated
No
Overload release current setting
1000.0 - 2500A
Number of auxiliary contacts as normally closed contact
0
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA071708R1 | E2.2S 2500 EKIP HI-TOUCH LSI 4P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
2500A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Rated voltage
690 .. 690V
Integrated earth fault protection
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
With switched-off indicator
Number of poles
4
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Motor drive optional
Degree of protection (IP)
IP30
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Back side
Type of control element
Push button
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
Motor drive integrated
Overload release current setting
1000.0 .. 2500A
Number of auxiliary contacts as normally closed contact
0