Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Rated voltage
690 - 690V
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Type of control element
Push button
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Overload release current setting
1000.0 - 2500A
Number of poles
4
Motor drive optional
Yes
Complete device with protection unit
Yes
Motor drive integrated
No
With switched-off indicator
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Number of auxiliary contacts as normally closed contact
0
Rated permanent current Iu
2500A
Integrated earth fault protection
No
Number of auxiliary contacts as normally open contact
0
From same serie
1SDA071705R1 | E2.2S 2500 EKIP TOUCH LSI 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Rated voltage
690 .. 690V
Device construction
Built-in device fixed built-in technique
Type of electrical connection of main circuit
Bolt connection
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Type of control element
Push button
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Overload release current setting
1000.0 .. 2500A
Number of poles
4
Motor drive optional
Complete device with protection unit
Motor drive integrated
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Number of auxiliary contacts as normally closed contact
0
Rated permanent current Iu
2500A
Integrated earth fault protection