Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
800A
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Overload release current setting
320.0 - 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
With under voltage release
No
Motor drive integrated
No
Number of poles
4
DIN rail (top hat rail) mounting optional
No
Type of control element
Push button
Motor drive optional
Yes
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Position of connection for main current circuit
Back side
Rated voltage
690 - 690V
Integrated earth fault protection
No
From same serie
1SDA071524R1 | E2.2N 800 EKIP TOUCH LI 4P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Bolt connection
Rated permanent current Iu
800A
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Overload release current setting
320.0 .. 800A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
With under voltage release
Motor drive integrated
Number of poles
4
DIN rail (top hat rail) mounting optional
Type of control element
Push button
Motor drive optional
Degree of protection (IP)
IP30
Complete device with protection unit
Position of connection for main current circuit
Back side
Rated voltage
690 .. 690V
Integrated earth fault protection
From same serie