Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Overload release current setting
252.0 - 630A
Adjustment range short-term delayed short-circuit release
378.0 - 6300A
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Number of poles
4
Integrated earth fault protection
Yes
With switched-off indicator
Yes
Device construction
Built-in device fixed built-in technique
Rated permanent current Iu
630A
Adjustment range undelayed short-circuit release
945.0 - 9450A
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
Type of control element
Push button
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
DIN rail (top hat rail) mounting optional
No
Motor drive optional
Yes
Position of connection for main current circuit
Back side
Motor drive integrated
No
Number of auxiliary contacts as normally open contact
0
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA071337R1 | E1.2B 630 EKIP G TOUCH LSIG 4P F

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Overload release current setting
252.0 .. 630A
Adjustment range short-term delayed short-circuit release
378.0 .. 6300A
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Number of poles
4
Integrated earth fault protection
With switched-off indicator
Device construction
Built-in device fixed built-in technique
Rated permanent current Iu
630A
Adjustment range undelayed short-circuit release
945.0 .. 9450A
Number of auxiliary contacts as normally closed contact
0
Type of electrical connection of main circuit
Bolt connection
Type of control element
Push button
Degree of protection (IP)
IP30
Complete device with protection unit
DIN rail (top hat rail) mounting optional
Motor drive optional
Position of connection for main current circuit
Back side
Motor drive integrated
Number of auxiliary contacts as normally open contact
0
From same serie