Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

3200A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Overload release current setting

1280.0 - 3200A

Adjustment range short-term delayed short-circuit release

1920.0 - 32000A

Rated voltage

690 - 690V

Type of electrical connection of main circuit

Bolt connection

Integrated earth fault protection

Yes

Adjustment range undelayed short-circuit release

4800.0 - 48000A

DIN rail (top hat rail) mounting optional

No

Number of auxiliary contacts as change-over contact

4

Device construction

Built-in device fixed built-in technique

With switched-off indicator

Yes

Suitable for DIN rail (top hat rail) mounting

No

With under voltage release

No

Position of connection for main current circuit

Back side

Complete device with protection unit

Yes

Motor drive integrated

No

Number of poles

3

Type of control element

Push button

Motor drive optional

Yes

Degree of protection (IP)

IP30


Warehouse states

Zagreb:

0 pcs

Zadar:

0 pcs


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA071176R1 | E4.2V 3200 EKIP TOUCH LSIG 3P FH

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

3200A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Overload release current setting

1280.0 .. 3200A

Adjustment range short-term delayed short-circuit release

1920.0 .. 32000A

Rated voltage

690 .. 690V

Type of electrical connection of main circuit

Bolt connection

Integrated earth fault protection

Adjustment range undelayed short-circuit release

4800.0 .. 48000A

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as change-over contact

4

Device construction

Built-in device fixed built-in technique

With switched-off indicator

Suitable for DIN rail (top hat rail) mounting

With under voltage release

Position of connection for main current circuit

Back side

Complete device with protection unit

Motor drive integrated

Number of poles

3

Type of control element

Push button

Motor drive optional

Degree of protection (IP)

IP30