

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
800.0 - 2000A
Adjustment range short-term delayed short-circuit release
1200.0 - 20000A
Rated permanent current Iu
2000A
Integrated earth fault protection
Yes
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive integrated
No
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Number of poles
3
Complete device with protection unit
Yes
Motor drive optional
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA071107R1 | E4.2V 2000 EKIP G TOUCH LSIG 3P

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
800.0 .. 2000A
Adjustment range short-term delayed short-circuit release
1200.0 .. 20000A
Rated permanent current Iu
2000A
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Number of auxiliary contacts as normally closed contact
0
Device construction
Built-in device fixed built-in technique
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive integrated
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Number of poles
3
Complete device with protection unit
Motor drive optional
From same serie
We use cookies to enhance your experience.