Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Integrated earth fault protection
No
Rated permanent current Iu
2500A
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
DIN rail (top hat rail) mounting optional
No
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Overload release current setting
1000.0 - 2500A
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Yes
Complete device with protection unit
Yes
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive integrated
No
Motor drive optional
Yes
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA071085R1 | E2.2H 2500 EKIP TOUCH LSI 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Integrated earth fault protection
Rated permanent current Iu
2500A
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Overload release current setting
1000.0 .. 2500A
Number of auxiliary contacts as normally closed contact
0
With switched-off indicator
Complete device with protection unit
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive integrated
Motor drive optional
Position of connection for main current circuit
Back side
Degree of protection (IP)
IP30
From same serie