

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Number of auxiliary contacts as change-over contact
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated permanent current Iu
2500A
Integrated earth fault protection
No
DIN rail (top hat rail) mounting optional
No
Overload release current setting
1000.0 - 2500A
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
3
Device construction
Built-in device fixed built-in technique
Rated voltage
690 - 690V
With switched-off indicator
Yes
Type of control element
Push button
Position of connection for main current circuit
Back side
Complete device with protection unit
Yes
Type of electrical connection of main circuit
Bolt connection
With under voltage release
No
Degree of protection (IP)
IP30
Motor drive optional
Yes
Motor drive integrated
No
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA071084R1 | E2.2H 2500 EKIP TOUCH LI 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Number of auxiliary contacts as change-over contact
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated permanent current Iu
2500A
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Overload release current setting
1000.0 .. 2500A
Suitable for DIN rail (top hat rail) mounting
Number of poles
3
Device construction
Built-in device fixed built-in technique
Rated voltage
690 .. 690V
With switched-off indicator
Type of control element
Push button
Position of connection for main current circuit
Back side
Complete device with protection unit
Type of electrical connection of main circuit
Bolt connection
With under voltage release
Degree of protection (IP)
IP30
Motor drive optional
Motor drive integrated
From same serie
We use cookies to enhance your experience.