Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Adjustment range short-term delayed short-circuit release
1200.0 - 20000A
Integrated earth fault protection
Yes
With switched-off indicator
Yes
Rated permanent current Iu
2000A
Number of auxiliary contacts as change-over contact
4
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Position of connection for main current circuit
Back side
Overload release current setting
800.0 - 2000A
Motor drive optional
Yes
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Bolt connection
Number of poles
3
Device construction
Built-in device fixed built-in technique
Motor drive integrated
No
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Type of control element
Push button
From same serie
1SDA071039R1 | E2.2N 2000 EKIP HI-TOUCH LSIG 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Adjustment range short-term delayed short-circuit release
1200.0 .. 20000A
Integrated earth fault protection
With switched-off indicator
Rated permanent current Iu
2000A
Number of auxiliary contacts as change-over contact
4
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Position of connection for main current circuit
Back side
Overload release current setting
800.0 .. 2000A
Motor drive optional
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Bolt connection
Number of poles
3
Device construction
Built-in device fixed built-in technique
Motor drive integrated
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Type of control element
Push button
From same serie