Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1600A
Rated voltage
690 - 690V
Overload release current setting
640.0 - 1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Integrated earth fault protection
Yes
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Number of poles
3
Motor drive integrated
No
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Back side
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive optional
Yes
Warehouse states
Zagreb:
0 pcs
Zadar:
0 pcs
From same serie
1SDA070990R1 | E2.2B 1600 EKIP G HI-TOUCH LSIG

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1600A
Rated voltage
690 .. 690V
Overload release current setting
640.0 .. 1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Integrated earth fault protection
Type of electrical connection of main circuit
Bolt connection
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Device construction
Built-in device fixed built-in technique
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Number of poles
3
Motor drive integrated
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Back side
Type of control element
Push button
Complete device with protection unit
Motor drive optional
From same serie