Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Integrated earth fault protection
Yes
Overload release current setting
320.0 - 800A
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Yes
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Position of connection for main current circuit
Back side
Rated voltage
690 - 690V
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
1200.0 - 12000A
Device construction
Built-in device fixed built-in technique
Rated permanent current Iu
800A
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Yes
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
480.0 - 8000A
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
From same serie
1SDA070896R1 | E2.2N 800 EKIP TOUCH LSIG 3P FHR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Integrated earth fault protection
Overload release current setting
320.0 .. 800A
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Type of electrical connection of main circuit
Bolt connection
With switched-off indicator
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Position of connection for main current circuit
Back side
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
1200.0 .. 12000A
Device construction
Built-in device fixed built-in technique
Rated permanent current Iu
800A
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
480.0 .. 8000A
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
From same serie